Generac 1505 RPM Sense Loss: What It Means & What To Do
Error 1505 — RPM Sensor Loss — is a cranking alarm. In Generac’s own description: the controller told the engine to crank, but got no signal back that the engine was actually turning. It triggers a shutdown every time it occurs and it will not self-clear. It is not one of the generic “low oil pressure” codes some listicles claim — those aggregators get this one wrong often enough that it’s worth saying out loud.
First, know which RPM code you have
The 1500 family splits on two axes — was the unit cranking or already running, and is the engine single- or two-cylinder:
- 1505 — 2-cylinder, cranking: no RPM signal during the start attempt.
- 1515 — 1-cylinder, cranking: same fault, smaller engine.
- 1501 — 2-cylinder, running: the unit was running and stalled or lost the signal (fuel, coils, or an overload stall lead that list).
- 1511 — 1-cylinder, running: same as 1501.
This article is about the cranking pair (1505/1515). If your unit starts and then dies with 1501/1511, the fuel branch leads — different tree.
The cause list, in the order technicians work it
Generac’s troubleshooting for this family is consistent across its documentation and its certified experts’ answers:
- The battery — bad, dead, improperly connected, or with loose or dirty terminals. This is cause #1 by a wide margin.
- The starter contactor — a small black relay near the controller with four wires; it converts the controller’s start signal into the higher-current signal that engages the starter solenoid. A fault or loose connection here stops the crank before it starts.
- The starter motor — a fault, a bad connection, or the small 16-gauge wire that signals the solenoid to engage being loose or disconnected.
- The ignition coils — defective, or damaged (they can contact the flywheel). The RPM signal itself reaches the controller from the coils on the 18-gauge wire — wire 18.
- The engine itself — internally damaged and physically unable to turn. Listed for completeness; it’s the rare branch.
The one question that splits the tree
Before touching anything, answer this from your last start attempt: what did the engine physically do?
- Click, or nothing: the crank never happened. Battery and connections first, then the contactor branch.
- Turns over slowly, labored: the classic battery-under-load signature (next section).
- Turns over at normal speed, then stops with the alarm: the engine turned but the controller never saw it — that’s the signal path (wire 18, coils), and after ruling out the battery it’s dealer diagnosis.
Why the battery fools everyone: resting voltage lies
Generac’s own troubleshooting guidance for this code is blunt: start with the battery, and load-test it — don’t just check voltage. A bad battery will very often show normal voltage at rest, then drop toward zero the moment a load is applied. The practical thresholds technicians use: sagging below roughly 10 volts during cranking points at the battery or its connections; a battery resting below about 12.4 volts that won’t recover on charge is a replacement. Terminals matter as much as the battery itself — clean to bright metal, tight, ground side included. Generator batteries live 3–5 years, and the correct replacement for Generac air-cooled units is a 12-volt Group 26R with at least 525 CCA. The full battery picture — including the charger faults that slowly murder good batteries — is in our low battery guide.
The documented reset for this family
Per Generac’s published guidance for RPM sense loss: clear the alarm by pressing ENTER twice, then press AUTO, remove some load, and restart in AUTO. If the unit starts and holds, watch it through its next exercise before calling it fixed — an intermittent 1505 that returns on cold mornings is telling you the battery story all over again.
Where the homeowner sequence ends
Battery proven good under load, terminals clean and tight, and the code still sets — the remaining causes (contactor tests, starter circuit, ignition coils, wire 18) are multimeter-and-manual work, and on a unit under warranty they’re the dealer’s work regardless: Generac-certified experts routinely warn that DIY repair beyond basic checks can void coverage. When you call, lead with the exact sentence this article gave you: “1505, cranks at normal speed” or “1505, just clicks” — it routes the technician to the right test first, which is real money on a visit that averages $273 before parts (Angi, Sept 2026).
If your code is actually 1100 — the engine cranks and cranks without the RPM complaint — that’s the fuel tree: see Generac Error Code 1100 Overcrank.
Sources: Generac Evolution e-Code reference (RPM Sensor Loss 1501/1505/1511/1515) and Generac Diagnostic Repair Manual (G0070420) via ManualsLib; Generac support reset guidance for the RPM sense loss family.